Power | 112.5 kV·A |
Dimensions | 31" X 39" x 48" |
Weight | 700 lbs. |
GE transformer
Catalog Number 9T10A1005, Type QL
112.5 KVA, 60HZ, 3 PH, 4.1% IMP
40C Amb., 150C Rise, 220C System, IS-19C
Primary (H) 480V (Line-Line)
Secondary (X) 208 (Line-Line)
120 (Line-Neutral)
Jumper Connections
Tap VOLTS
1-2 503
2-3 494
3-4 480
4-5 467
5-6 458
6-7 445
7-8 431
Net weight 680 Lbs., 68055, DY75A, NP3, 032217
Enclosure Type 2 (IP20). or rainproof Type 3R (IP22) when provided shield 9T18Y1074G06
before handling, Installing and Operating, See instruction 475A667AAP001 Outline:
Aluminum Conductor Primary: 10KV BIL Secondary: 1-KV BIL 3038111GEDYP75A
IN ACCORDANCE WITH SECTION 450-9, ALOW AT LEAST SIX INCHES CLEARANCE FOR VENTALATION.
CHECK ADDITIONAL NEC AND LOCAL CODE
GE Energy Industrial solutions, NEMA Class AA dry type Transformer Meets DOE 2016 Efficiency